Air gap, mm | 0 | 2 | 4 | 6 | 10 | 15 | 20 |
Diameter of rod/conductor, mm | <16 | 16.1 | 16.5 | 17.1 | 18.8 | 21.9 | 25.6 |
Conductor length | 3m | 250 | 350 | 450 | 500 | 600 | 650 | 700 |
10m | 250 | 370 | 500 | 600 | 700 | 800 | 900 | |
20m | 350 | 400 | 600 | 700 | 900 | 1000 | 1000 |
REFERENCE | VALUE |
EARTHING CONDUCTOR DIAMETER RANGE, mm | 5 to 16 | 35 to 150mm² |
EARTHING RIBBON, MAX, mm x mm | 20 mm x 60 mm |
MAXIMUM DISTANCE BETWEEN DISPLAY AND SENSOR | 20 m |
INSTALLATION ON THE CONDUCTOR | in parallel – clamped |
MINIMUM DISCHARGE PEAK CURRENT DETECTED - 8/20us waveform - IEC 62561-6 | 250 (500*) A |
MAXIMUM DISCHARGE PEAK CURRENT DETECTED - 10/350us waveform - IEC 62561-6 | 100 kA |
MINIMUM NUMBER STROKE REGISTRATION RATE | >= 2 counts/sec. |
MINIMUM TIME BETWEEN 2 STROKE FOR REGISTRATION, RESPONSE TIME | 20ms |
VOLTAGE DROP ON TERMINALS | < 1 V |
LONG DURATION CURRENT WITHSTAND CAPABILITY | 2500A for 4ms |
HIGH CURRENT WITHSTAND CAPABILITY | 100 kA |
FREQUENCY, Hz | 47 to 63 |
NUMBER OF DIGITS ON DISPLAY | 6 |
TYPE OF DISPLAY | MECHANICAL |
BATTERY POWER SUPPLY | NO |
SELF POWERED | YES |
RESET COUNTER METHOD | NO |
MEMORY ROM - Storage of last counter value | NO |
WEIGHT, kg | 1 Kg |
TEMPERATURE - °C | Class C2: -40 to +70 |
PROTECTION CLASS | IP67, NEMA 4X |
TEMPERATURE CHANGE RATE - °C/min | Class C2: 1,0 |
RELATIVE HUMIDITY - % | Class C2: 10 to 100 |
MAX ABSOLUTE HUMIDITY - g/m3 | Class C2: 35 |
MAX ALTITUDE - m | 2000 |
ATMOSPHERIC PRESSURE - kPa | 70 to 106 |
STANDARDS/TEST | IEC 62561-6:2018 |
LABEL INCLUDES | Hardware version number, serial number, manufacturing batch |
UV STABILIZED HOUSING | YES |
STAINLESS METAL | YES |
TYPE OF SURGE COUNTER as per IEC 62561-6:2018 | Type 1 and |