REFERENCE | VALUE |
EARTHING CONDUCTOR DIAMETER RANGE, mm | 5 to 16 mm (Outdoor version) 2 to 12 mm (Indoor version) |
MAXIMUM DISTANCE BETWEEN DISPLAY AND SENSOR | 20 m |
INSTALLATION ON THE CONDUCTOR | in parallel – clamped |
MINIMUM DISCHARGE PEAK CURRENT DETECTED - 8/20us waveform - IEC 62561-6 | 250 A |
MAXIMUM DISCHARGE PEAK CURRENT DETECTED - 10/350us waveform - IEC 62561-6 | 100 kA |
MINIMUM NUMBER STROKE REGISTRATION RATE | >= 2 counts/sec. |
MINIMUM TIME BETWEEN 2 STROKE FOR REGISTRATION, RESPONSE TIME | 50ms |
VOLTAGE DROP ON TERMINALS | < 1 V |
LONG DURATION CURRENT WITHSTAND CAPABILITY | 2500A for 4ms |
HIGH CURRENT WITHSTAND CAPABILITY | 100 kA |
FREQUENCY, Hz | 47 to 63 |
NUMBER OF DIGITS ON DISPLAY | 6 |
TYPE OF DISPLAY | MECHANICAL |
BATTERY POWER SUPPLY | NO |
SELF POWERED | YES |
RESET COUNTER METHOD | NO |
MEMORY ROM - Storage of last counter value | NO |
WEIGHT, kg | 0.5 Kg |