LLPD d45z up to 52kV

  • Protection against:
Direct Lightning Strike,
Induced overvoltage,
Back Flashover

  • Highest voltage for equipment, kV52
  • Maximum prospective fault current, kA5.0
  • Lightning discharge capability, C2.8
  • Installation1, 2 or 3 pcs per pole
post, pin-post insulation with d10z
This device is there to protect important networks from direct lightning strikes and back flashovers. Indented to be installed along the protected line, it works perfectly on distribution (sub-transmission) lines with the highest voltage of equipment up to 52 kV.
D45z can easily be adapted to poles/towers of totally different configuration. This is possible due to various installation options.
Electrical line parameters

Highest voltage for equipment*, kV

52

Maximum prospective fault current, kA

5

External air gap, mm

80+80

50% flashover voltage, kV (80+80 mm air gap)

<280

Power frequency withstand voltage**, kV (wet/dry)

95/95


Lightning parameters

Lightning discharge capability (200 μs)***, C

2.8

High current impulse (4/10 μs), kA

65

Maximum quenching lightning current, kA

20 (8/50µs)

Minimum withstand amount of operations

10


General Parameters

Additional power losses on the line, %

0

Average expected lifespan, years

30

UV resistance****, h

1000

Weight, kg

7

Maintenance

1 visual verification/year


* According to IEC 60038, ** According to IEC 60071-1, *** According toIEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
Examples of installation methods