LLPD dC20z up to 24 kV

This device has been specifically developed for the protection of overhead distribution lines from direct lightning strikes, back flashovers and induced overvoltages.
  • Protection against:
Direct Lightning Strike,
Induced overvoltage,
Back Flashover

  • Highest voltage for equipment, kV24
  • Maximum prospective fault current, kA5.0
  • Lightning discharge capability, C2.8
  • Installation1, 2 or 3 pcs per pole
post, pin-post insulation with d10z
LLPD dC20z is aimed to provide cost-effective and innovative lightning protection of overhead power lines. It means that with these devices installed your power network will be secure from direct lightning strikes, back flashovers and induced overvoltages and damage caused by their deleterious consequences.
This device is a representative of the range of products by Streamer, which has been specifically developed for the protection of overhead distribution lines from direct lightning strikes, back flashovers as well as induced overvoltages. It helps to keep power distribution lines safe from insulator/conductor breakages, switchgear trips, and outages.
Electrical line parameters

Highest voltage for equipment*, kV

24

Maximum prospective fault current, kA

5

External air gap, mm

60-80

50% flashover voltage (80 mm air gap), kV

<185

Power frequency withstand voltage**, kV (wet/dry)

40/50


Lightning parameters

Lightning discharge capability (200 μs)***, C

2.8

High current impulse (4/10 μs), kA

65

Maximum quenching lightning current, kA

20 (8/50µs)

Minimum withstand amount ofoperations

10


General Parameters

Additional power losses on the line, %

0

Average expected lifespan, years

30

UV resistance****, h

1000

Weight, kg

2.6

Maintenance

1 visual verification/year


* According to IEC 60038, ** According to IEC 60071-1, *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
Examples of installation methods