LLPD dM35z up to 40.5kV

  • Protection against:
Direct Lightning Strike,
Induced overvoltage,
Back Flashover

  • Highest voltage for equipment, kV40.5
  • Maximum prospective fault current, kA5.0
  • Lightning discharge capability, C2.8
  • Installation1, 2 or 3 pcs per pole
post, pin-post insulation with d10z
This device is designed to protect power supply networks from the consequences of either direct lightning strikes or induced overvoltages. Indented to be installed along the protected line, it works perfectly on distribution lines with the highest voltage of equipment up to 40.5 kV.
Line lightning protection device dM35z has successfully passed different tests in a number of laboratories, including a full series of test at CESI (Milano) in 2019, which confirms its ultimate reliability. It also enables the expected life time to be up to decades.
Electrical line parameters

Highest voltage for equipment*, kV

40.5

Maximum prospective fault current, kA

5

External air gap, mm

115-180

50% flashover voltage (180 mm air gap), kV

<200

Power frequency withstand voltage**, kV (wet/dry)

65/80


Lightning parameters

  Lightning discharge capability (200 μs)***, C

2.8

   High current impulse (4/10 μs), kA

65

   Maximum quenching lightning current, kA

20 (8/50 µs)

   Minimum withstand amount of operations

10


General Parameters 

Additional power losses on the line, %

0

Average expected lifespan, years

30

 UV resistance****, h

1000

 Weight, kg

 6.2

 Maintenance

1 visual verification/ year


* According to IEC 60038, ** According to IEC 60071-1, *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
Examples of installation methods